UFC 3-430-05 is the Unified Facilities Criteria for Natural Gas and Liquefied Petroleum Gas (LPG) Distribution Pipelines, current as of 26 February 2021 [UFC 3-430-05].
This UFC provides guidance for the design and installation of new or modifications to existing distribution pipelines conveying natural gas, manufactured gas, or LPG [UFC 3-430-05]. It supersedes UFC 3-430-09 (Exterior Mechanical Utility Distribution, dated 16 January 2004) [UFC 3-430-05].
Air Force implementation requires that natural gas and LPG distribution systems comply with UFC 3-430-05, which itself implements DOT Pipeline and Hazardous Materials Safety Administration standards (49 CFR Part 192). LPG systems must additionally comply with NFPA 58, and natural gas interior piping must comply with NFPA 54 [DAFMAN 32-1067 para 8.1.1].
For buried nonmetallic piping, an electrically conductive wire or tape must be buried within 12 inches above the pipe for locating purposes [DAFMAN 32-1067 para 8.1.1].
Unofficial — answered from indexed publication text, which may be incomplete or out of date. Your MAJCOM/unit supplement may be stricter. Verify the official PDF before acting or writing a finding.
DAFMAN 32-1067 para 8.1.1, p. 37 (effective/current as of 2025-08-01)ordance with UFC 3-430-05, Natural Gas and Liquefied Petroleum Gas (LPG) Distribution Pipelines, which complies with DOT Pipeline and Hazardous Materials Safety Administration and 49 CFR Part 192, Transportation of Natural and Other Gas by Pipeline: Minimum Federal Safety Standards. LPG distribution systems must comply with NFPA 58, Liquefied Petroleum Gas Code. LNG plants must comply with NFPA 59A, Standard for the Production, Storage, and Handling of Liquefied Natural Gas (LNG). Natural gas distribution systems and interior piping must comply with NFPA 54, National Fuel Gas Code. (T-0) 8.1.1. Buried Piping. Nonmetallic buried piping must have an electrically conductive wire or tape buried within 12 inches (305 millimeters) above the pipe as a means for locating the pipe. (T-0) High-densi
No supplement passage retrieved — check the supplement chain on the pub page before citing.
No federal/DoD passage retrieved.